Model
|
DR-100-12
|
DR-100-15
|
DR-100-24
|
OUTPUT
|
DC Voltage
|
12V
|
15V
|
24V
|
Rated Current
|
7.5A
|
6.5A
|
4.2A
|
Current Range
|
0-7.5A
|
0-6.5A
|
0-4.2A
|
Rated Power
|
90W
|
97.5W
|
100.8W
|
Ripple & Noise (max.) Note.2
|
120mVp-p
|
120mVp-p
|
150mVp-p
|
Voltage Adj. Range
|
12-15V
|
15-18V
|
24-29V
|
Voltage Tolerance Note.3
|
±2%
|
±1%
|
±1%
|
LINE REGULATION
|
±1%
|
±1%
|
±1%
|
LOAD REGULATION
|
±1%
|
±1%
|
±1%
|
Setup, Rise Time
|
2700ms, 80ms/230VAC 2700ms, 80ms/115VAC at full load
|
Hold Up Time
|
50ms/230VAC 18ms/115VAC at full load
|
INPUT
|
Voltage Range
|
88 ~ 264VAC 124 ~ 370VDC
|
FREQUENCY RANGE
|
47~63Hz
|
AC Current
|
3A/115VAC 1.6A/230VAC
|
Efficiency
|
87%
|
87%
|
89%
|
Inrush Current
|
COLD START 30A/115VAC 45A/230VAC
|
PROTECTION
|
Over Load
|
105%~135% rated output power
|
Protection type: Constant current limiting, recovers automatically after fault condition is removed
|
Over Voltage
|
16 ~ 20V
|
19 ~ 23V
|
30 ~ 35V
|
Protection type : Shut down o/p voltage, re-power on to recover
|
OVER TEMPERATURE
|
90°C± 15°C (RTH2) detect on heat sink of power transistor
|
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
|
ENVIRONMENT
|
Working Temp.,
|
-20°C~+60°C; (Refer to "Derating Curve")
|
WORKING HUMIDITY
|
20 ~ 90% RH non-condensing
|
Storage Temp., Humidity
|
-40°C~+85°C; 10%~95%RH
|
Temp. Coefficient
|
±0.03%/°C(0~50°C)
|
Vibration
|
10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes
|
SAFETY
|
Withstand Voltage
|
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
|
Isolation Resistance
|
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C / 70% RH
|
EMC EMISSION
|
Compliance to EN55011, EN55022 (CISPR22) Class B, EN61000-3-2,-3
|
EMC IMMUNITY
|
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
|
OTHERS
|
MTBF
|
486K hrs min. MIL-HDBK-217F (25°C )
|
DIMENSION
|
100*93*56mm (W*H*D)
|
NOTE
|
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be reconfirmed that it still meets
EMC directives.
5. Harmonic current test @ 90% load.
6. Under short circuit or overload >150% conditions, output voltage may shut down for 5 sec
|